BE1-11g
PERFORMANCE SPECIFICATIONS, continued
SETTING GROUPS
Setting Groups: 4
Control Modes: Automatic: CLP
Dynamic load or unbalance
External: Discrete input logic;
Binary: Input Logic
METERING
Current Range: 5A 0.5 to 15.0
1A 0.1 to 3.0
Current Accuracy: ±1%
Phase Voltage Range: 3W 0 - 300 V
L-L
4W 0 - 300 V
L-L
Phase Voltage Accuracy: ±0.5% for
50V<V
L-L
<300V
Watt/VAR: 5A 0 to ±7500
1A 0 to ±1500
Watt Accuracy: 1% @ Unity PF
VAR Accuracy: 1% @ Zero PF
Energy: 0 to ±1.0E12
(F/R registers)
Frequency: 10 - 75Hz
Frequency Accuracy: 0.01Hz
DEMANDS (IA, IB, IC, IN, IQ, Fwd Watts, Rvs Watts,
Fwd VARs, Rvs VARs)
Demand Interval: 1 - 60 min.
Demand Mode: Thermal
BREAKER MONITORING
Duty Mode: I or I
2
Duty Alarm Range: 0 - to 100%
Op Counter Alarm Range: 0 - 99999
Trip Time Alarm Range: 20 - 1000mSec