BE1-87G
• Minimum Differential (Operate) Current
• 0.1, 0.15, 0.2, 0.4, 0.5, 0.8, 1.6 A
• Accuracy
• For IR ≤ 4 A: ±5% of operate pickup or ±25 mA
(whichever is greater)
• For IR > 6 A (20 A max.): ±8% of operate pickup or
±150 mA (whichever is greater)
• Dropout
• > 90% of operate characteristic
• Timing
• < 30 ms at 10 times pickup setting; 70 ms maximum
Sensing-Range 1
Page 1-5