AW00101404000 Installation Guide
Basler IP Fixed Dome Cameras 41
EnglishLanguageLanguageLanguageLanguageLanguageLanguageLanguage
8 The RS-485 Terminal Block
The 3-hole terminal block on the right side of the camera base can be used to
make an RS-485 connection to the camera.
The assignments for the wire fixing holes in the terminal block are as shown
below. The A+, B-, and Gnd connections are standard for an RS-485
connection. The RS-485 ground is isolated from the camera’s power ground
and I/O ground.
Fig. 5: RS-485 Terminal Block
The terminal block is a push-in type of connector. Either solid or stranded wires
can be inserted into the wire fixing holes in the terminal block. A wire can be
removed from a fixing hole by pressing the release tab above the hole and
pulling on the wire.
Wires inserted into the fixing holes must have a minimum cross section of 0.2
mm
2
(AWG 24) and a maximum cross section of 1.5 mm
2
(AWG 16).
8 mm (5/16") of insulation should be stripped from the end of a wire before it
is inserted into a fixing hole.
Wire
Fixing
Holes
Release
Tabs